Published March 2, 2015 | Version v1
Journal article Open

Spatial and Temporal Variations in Indoor Environmental Conditions, Human Occupancy, and Operational Characteristics in a New Hospital Building

  • 1. Illinois Institute of Technology
  • 2. University of Toronto
  • 3. University of Chicago

Description

The dynamics of indoor environmental conditions, human occupancy, and operational characteristics of buildings influence human comfort and indoor environmental quality, including the survival and progression of microbial communities. A suite of continuous, long-term environmental and operational parameters were measured in ten patient rooms and two nurse stations in a new hospital building in Chicago, IL to characterize the indoor environment in which microbial samples were taken for the Hospital Microbiome Project. Measurements included environmental conditions (indoor dry-bulb temperature, relative humidity, humidity ratio, and illuminance) in the patient rooms and nurse stations; differential pressure between the patient rooms and hallways; surrogate measures for human occupancy and activity in the patient rooms using both indoor air CO2 concentrations and infrared doorway beam-break counters; and outdoor air fractions in the heating, ventilating, and air-conditioning systems serving the sampled spaces. Measurements were made at 5-minute intervals over consecutive days for nearly one year, providing a total of ∼8×106 data points. Indoor temperature, illuminance, and human occupancy/activity were all weakly correlated between rooms, while relative humidity, humidity ratio, and outdoor air fractions showed strong temporal (seasonal) patterns and strong spatial correlations between rooms. Differential pressure measurements confirmed that all patient rooms were operated at neutral pressure. The patient rooms averaged about 100 combined entrances and exits per day, which suggests they were relatively lightly occupied compared to higher traffic environments (e.g., retail buildings) and more similar to lower traffic office environments. There were also clear differences in several environmental parameters before and after the hospital was occupied with patients and staff. Characterizing and understanding factors that influence these building dynamics is vital for hospital environments, where they can impact patient health and the survival and spread of healthcare associated infections.

Data availability

All data files are available from the IIT Digital Repository: http://repository.iit.edu/handle/10560/3272.

Files

journal.pone.0118207.pdf

Files (38.3 MB)

Name Size Download all
Article
md5:55a8bb5e6b1f57676e452c2f5d112107
4.4 MB Preview Download
md5:7cb13fd37e2d9c32c1554a9dd9cefa5f
34.0 MB Preview Download

Additional details

Identifiers

DOI
10.1371/journal.pone.0118207
Other
oai:uchicago.tind.io:10409

Funding

Alfred P. Sloan Foundation
program on the Microbiology of the Built Environment
Starr-Fieldhouse
Research Fellowship

UChicago Information

Division(s)
Biological Sciences Division
Department(s)
Ecology and Evolution